Surge protection device, class 1+2 (B+C), Iimp=25 kA, Uc=280 VAC, 4-pole, with remote-signal contact
- Category
- SPD
- Code
- 105508
- Manufacturer
- Noark
| System configuration IT | NO |
| Exhausting | NO |
| Lightning impulse current (10/350) | 25 |
| Max conductor cross section solid (solid, stranded) | 50 |
| Max conductor cross section flexible | 50 |
| Signalling at the device | Optic |
| System configuration TN-S | YES |
| Voltage protection level L-N | 1.5 |
| Voltage protection level N-PE | 1.5 |
| Test class | Type 1 + 2 |
| Integrated backup fuse | NO |
| System configuration TN | YES |
| System configuration other | NO |
| Number of poles | 4 |
| System configuration TT | NO |
| Specific energy (W/R) | 156 |
| Remote signalling | YES |
| Energy-coordinated protection effect with regard to the terminal equipment | NO |
| Max. continuous voltage AC | 280 V |
| Nominal voltage AC | 280 V |
| System configuration DC | NO |
| System configuration TN-C | NO |
| System configuration TN-C-S | YES |
| Mounting method DINrail | 35 mm |